AVB โ Atmospheric Vacuum Breaker
Cheapest and simplest. Permitted only where the downstream system cannot be pressurized for more than 12 consecutive hours. Cannot be installed downstream of any shutoff valve. NOT acceptable for reclaimed water in FL.
LOW hazard only
Simple residential
PVB โ Pressure Vacuum Breaker
Most common for FL residential irrigation on potable water. Must be installed at least 12" above the highest downstream outlet. Requires annual testing. Acceptable where shutoff valves are downstream. Not allowed for reclaimed water.
Moderate hazard
Standard FL residential
DC โ Double Check Valve Assembly
Two independently operating check valves with test cocks and shutoffs. Good for below-grade installation. Acceptable for low-to-moderate hazard commercial irrigation. Not acceptable for reclaimed water or high hazard applications. Requires annual testing.
Low-moderate hazard
Commercial irrigation
RP โ Reduced Pressure Zone Backflow Preventer
Highest protection level. Required for all reclaimed water irrigation in FL (FAC 62-610). Also required for commercial potable irrigation in many FL counties and for any high-hazard connection. Must be installed above grade. Requires annual testing.
High hazard / reclaimed
Reclaimed water required